UPS Runtime Calculator

Enter the battery capacity, voltage and number of batteries, plus the load. The calculator estimates the runtime.

Quick answer: Battery Wh = Ah × volts × number of batteries. For example, with battery capacity of 9 Ah, battery voltage of 12 V and number of batteries of 1, the estimated runtime is 22 min.

How the UPS Runtime calculation works

  • Battery Wh = Ah × volts × number of batteries
  • Runtime (h) = Wh × efficiency × usable share ÷ load

How long a UPS lasts

Runtime ≈ battery energy × usable share × efficiency ÷ load. A single 12 V 9 Ah battery holds 108 Wh; at 200 W, with 80% usable and 85% efficiency, it runs about 22 minutes.

Small UPS batteries deliver less than their rating at high loads (the Peukert effect), so treat the result as an upper estimate.

Getting more runtime

  • Plug only essentials into the battery outlets: computer, monitor, router.
  • Turn off the monitor or let the computer sleep during outages.
  • Replace UPS batteries every 3–5 years — capacity fades with age.

For longer backup, see the Battery Backup Calculator.

What you need for the UPS Runtime Calculator

Battery capacityA number (Ah).
Battery voltageA number (V).
Number of batteriesA whole number.
LoadA number (W).
Inverter efficiencyA percentage.
Usable battery capacityA percentage.

How to use the UPS Runtime Calculator

  1. Check the Region line at the top of the calculator. Your country, currency and units are detected automatically; change them if needed.
  2. Enter battery capacity, battery voltage, number of batteries, load, inverter efficiency and usable battery capacity. Example values are filled in so you can see how it works.
  3. Read your result: the estimated runtime appears instantly, with battery energy underneath.
  4. Use Copy result, Share link or Print to keep the answer. Nothing you type is sent to our servers.

UPS Runtime calculation example

Using the calculator’s example values (shown in US dollars and metric units — the calculator itself adapts to your country):

Inputs
Battery capacity9 Ah
Battery voltage12 V
Number of batteries1
Load200 W
Inverter efficiency85%
Usable battery capacity80%
Results
Estimated runtime22 min
Battery energy108 Wh

What affects the UPS runtime result most

We re-ran the example with each input 10% higher to see which ones move the estimated runtime most:

  1. If battery capacity is 10% higher, the estimated runtime rises by 10% to 24 min.
  2. If battery voltage is 10% higher, the estimated runtime rises by 10% to 24 min.
  3. If inverter efficiency is 10% higher, the estimated runtime rises by 10% to 24 min.

Focus on the first of these when you want to change the result. The calculator shows the biggest lever for your own numbers under the result.

Assumptions and limitations of the UPS Runtime Calculator

  • Constant load; new, fully charged batteries at room temperature.

Limitations

  • Results are estimates based on the numbers you enter. Check important decisions with a qualified professional.

Estimates only. Actual consumption depends on the appliance, settings, climate and your tariff structure.

UPS Runtime Calculator FAQs

How long will my UPS last?

A small 12 V 9 Ah UPS battery runs a 200 W computer for about 20 minutes.

Why does runtime fall faster at high loads?

Batteries deliver less of their rated capacity when discharged quickly.

How often should UPS batteries be replaced?

Sealed lead-acid UPS batteries typically last 3–5 years.

Why is my UPS runtime shorter than expected?

Aging batteries, high loads and heat all reduce runtime. Test it under real load every few months.

What formula does the UPS Runtime Calculator use?

Battery Wh = Ah × volts × number of batteries. Runtime (h) = Wh × efficiency × usable share ÷ load.

What do I need to use the UPS Runtime Calculator?

You need battery capacity, battery voltage, number of batteries, load, inverter efficiency and usable battery capacity. Example values are pre-filled, and the calculator converts between metric and imperial units and any currency.

What affects the UPS runtime result most?

If battery capacity is 10% higher, the estimated runtime rises by 10% to 24 min. If battery voltage is 10% higher, the estimated runtime rises by 10% to 24 min.

Embed this calculator on your website

Free for any website or blog. Paste this code where the calculator should appear — it resizes itself and needs no sign-up.