Enter the power you need during an outage, for how long, the battery voltage and type. The calculator gives the battery capacity required.

Quick answer: Energy needed = load × hours ÷ inverter efficiency. For example, with load during backup of 500 W, backup time needed of 4 h and inverter efficiency of 90%, the battery capacity needed is 370 Ah.

How the Battery Backup calculation works

  • Energy needed = load × hours ÷ inverter efficiency
  • Battery Wh = energy needed ÷ depth of discharge
  • Battery Ah = Wh ÷ voltage

Sizing a battery bank

Battery capacity = load × hours ÷ (voltage × usable depth of discharge × efficiency). Running 500 W for 4 hours from a 12 V lead-acid bank used to 50% needs about 370 Ah — for example three 150 Ah batteries.

Lithium (LiFePO4) batteries can be used to 80–90%, so the same load needs far less capacity: 300 W for 3 hours at 80% depth needs about 104 Ah.

Battery tips

  • Deep discharges shorten lead-acid battery life; stay near 50%.
  • Use a higher system voltage (24 V or 48 V) for larger loads to reduce current and cable size.
  • Tubular lead-acid batteries suit Indian home inverters with frequent outages.

Size the inverter to match with the Inverter Size Calculator.

What you need for the Battery Backup Calculator

Load during backupA number (W).
Backup time neededA number (h).
Battery bank voltageChoose one: 12 V; 24 V; 48 V.
Battery type (usable depth of discharge)Choose one: Lead-acid / tubular (50%); Lithium LFP (80%); Lithium LFP (90%).
Inverter efficiencyA percentage.

How to use the Battery Backup Calculator

  1. Check the Region line at the top of the calculator. Your country, currency and units are detected automatically; change them if needed.
  2. Enter load during backup, backup time needed, battery bank voltage, battery type (usable depth of discharge) and inverter efficiency. Example values are filled in so you can see how it works.
  3. Read your result: the battery capacity needed appears instantly, with battery energy and energy delivered to the load underneath.
  4. Use Copy result, Share link or Print to keep the answer. Nothing you type is sent to our servers.

Battery Backup calculation example

Using the calculator’s example values (shown in US dollars and metric units — the calculator itself adapts to your country):

Inputs
Load during backup500 W
Backup time needed4 h
Battery bank voltage12 V
Battery type (usable depth of discharge)Lead-acid / tubular (50%)
Inverter efficiency90%
Results
Battery capacity needed370 Ah
Battery energy4,444 Wh
Energy delivered to the load2,000 Wh
  • For example: 3 × 150 Ah batteries at 12 V.

What affects the battery backup result most

We re-ran the example with each input 10% higher to see which ones move the battery capacity needed most:

  1. If load during backup is 10% higher, the battery capacity needed rises by 10% to 407 Ah.
  2. If backup time needed is 10% higher, the battery capacity needed rises by 10% to 407 Ah.
  3. If inverter efficiency is 10% higher, the battery capacity needed falls by 9.1% to 337 Ah.

Focus on the first of these when you want to change the result. The calculator shows the biggest lever for your own numbers under the result.

Assumptions and limitations of the Battery Backup Calculator

  • Constant load. Lead-acid capacity falls at high discharge rates and low temperatures.

Limitations

  • Results are estimates based on the numbers you enter. Check important decisions with a qualified professional.

Estimates only. Actual consumption depends on the appliance, settings, climate and your tariff structure.

Battery Backup Calculator FAQs

How many batteries do I need for a 1 kW load for 4 hours?

About 4.4 kWh of usable energy after inverter losses; with lead-acid at 50% depth that is roughly 8.9 kWh of battery — about 740 Ah at 12 V.

Why only use 50% of a lead-acid battery?

Discharging deeper shortens its life sharply. Lithium batteries tolerate 80–90%.

Should I use 12 V or 48 V?

Higher voltage means lower current, thinner cables and better efficiency for larger systems.

How long will a 150 Ah battery last?

A 12 V 150 Ah lead-acid battery used to 50% supplies about 900 Wh — roughly 3 hours at 300 W, less with losses.

What formula does the Battery Backup Calculator use?

Energy needed = load × hours ÷ inverter efficiency. Battery Wh = energy needed ÷ depth of discharge. Battery Ah = Wh ÷ voltage.

What do I need to use the Battery Backup Calculator?

You need load during backup, backup time needed, battery bank voltage, battery type (usable depth of discharge) and inverter efficiency. Example values are pre-filled, and the calculator converts between metric and imperial units and any currency.

What affects the battery backup result most?

If load during backup is 10% higher, the battery capacity needed rises by 10% to 407 Ah. If backup time needed is 10% higher, the battery capacity needed rises by 10% to 407 Ah.