Enter the power you need during an outage, for how long, the battery voltage and type. The calculator gives the battery capacity required.
Quick answer: Energy needed = load × hours ÷ inverter efficiency. For example, with load during backup of 500 W, backup time needed of 4 h and inverter efficiency of 90%, the battery capacity needed is 370 Ah.
Battery capacity = load × hours ÷ (voltage × usable depth of discharge × efficiency). Running 500 W for 4 hours from a 12 V lead-acid bank used to 50% needs about 370 Ah — for example three 150 Ah batteries.
Lithium (LiFePO4) batteries can be used to 80–90%, so the same load needs far less capacity: 300 W for 3 hours at 80% depth needs about 104 Ah.
Size the inverter to match with the Inverter Size Calculator.
| Load during backup | A number (W). |
|---|---|
| Backup time needed | A number (h). |
| Battery bank voltage | Choose one: 12 V; 24 V; 48 V. |
| Battery type (usable depth of discharge) | Choose one: Lead-acid / tubular (50%); Lithium LFP (80%); Lithium LFP (90%). |
| Inverter efficiency | A percentage. |
Using the calculator’s example values (shown in US dollars and metric units — the calculator itself adapts to your country):
| Load during backup | 500 W |
|---|---|
| Backup time needed | 4 h |
| Battery bank voltage | 12 V |
| Battery type (usable depth of discharge) | Lead-acid / tubular (50%) |
| Inverter efficiency | 90% |
| Battery capacity needed | 370 Ah |
|---|---|
| Battery energy | 4,444 Wh |
| Energy delivered to the load | 2,000 Wh |
We re-ran the example with each input 10% higher to see which ones move the battery capacity needed most:
Focus on the first of these when you want to change the result. The calculator shows the biggest lever for your own numbers under the result.
Estimates only. Actual consumption depends on the appliance, settings, climate and your tariff structure.
About 4.4 kWh of usable energy after inverter losses; with lead-acid at 50% depth that is roughly 8.9 kWh of battery — about 740 Ah at 12 V.
Discharging deeper shortens its life sharply. Lithium batteries tolerate 80–90%.
Higher voltage means lower current, thinner cables and better efficiency for larger systems.
A 12 V 150 Ah lead-acid battery used to 50% supplies about 900 Wh — roughly 3 hours at 300 W, less with losses.
Energy needed = load × hours ÷ inverter efficiency. Battery Wh = energy needed ÷ depth of discharge. Battery Ah = Wh ÷ voltage.
You need load during backup, backup time needed, battery bank voltage, battery type (usable depth of discharge) and inverter efficiency. Example values are pre-filled, and the calculator converts between metric and imperial units and any currency.
If load during backup is 10% higher, the battery capacity needed rises by 10% to 407 Ah. If backup time needed is 10% higher, the battery capacity needed rises by 10% to 407 Ah.